Step | Action | Value(s) | Yes | No |
---|---|---|---|---|
1 | Was the entire HVAC System Check performed? | -- | Go to Step 2 | Go to HVAC System Check |
2 |
Does the measured voltage vary between approximately 1 and 12 volts? | 1-12 V | Go to Step 3 | Go to Step 4 |
3 | Using a J 39200 , probe between the auxiliary heater-A/C control connector C1 terminal 1 and ground. Is the measured voltage within the specified values? | 9-14 V | Go to Step 5 | Go to Step 6 |
4 | Repair the poor connection or open in CKT 733 between S252 and the auxiliary heater-A/C control connector C1 terminal 4. Is the repair complete? | -- | Go to Step 15 | -- |
5 | Using a J 39200 , probe between the auxiliary heater-A/C control connector C1 terminal 6 and B+. Is the measured voltage within the specified values? | 9-14 V | Go to Step 8 | Go to Step 7 |
6 | Repair the poor connection or open in circuit 641 between the auxiliary heater-A/C control connector C1 terminal 1 and S345. Is the repair complete? | -- | Go to Step 15 | -- |
7 | Repair the open in CKT 850 between the auxiliary heater-A/C control connector C1 terminal 6 and S403. Is the repair complete? | -- | Go to Step 15 | -- |
8 |
Was replacement of the auxiliary heater-A/C control necessary? | -- | Go to Step 15 | Go to Step 9 |
9 | Repair the poor connection or short to ground in CKT 955. Is the repair complete? | -- | Go to Step 10 | -- |
10 | Using a J 39200 , probe between the temperature valve actuator connector terminal 10 and ground. Is the measured voltage within the specified values? | 9-14 V | Go to Step 11 | Go to Step 12 |
11 | Using a J 39200 , probe between the auxiliary temperature valve actuator connector terminal 7 and B+. Is the voltage within the specified values? | 9-14 V | Go to Step 13 | Go to Step 14 |
12 | Repair the poor connection or open in CKT 641 between the auxiliary temperature valve actuator connector terminal 10 and S345. Is the repair complete? | -- | Go to Step 15 | -- |
13 | Replace the auxiliary temperature valve actuator. Refer to Temperature Actuator Replacement - Auxiliary . Is the repair complete? | -- | Go to Step 15 | -- |
14 | Repair the open in CKT 850 between the auxiliary temperature valve actuator connector terminal 7 and S403. Is the repair complete? | -- | Go to Step 15 | -- |
15 |
Have all the repairs been made? | -- | Go to HVAC System Check | -- |