Step | Action | Yes | No | ||||||
---|---|---|---|---|---|---|---|---|---|
DEFINITION: The low and the high side pressures are both higher than normal.
| |||||||||
1 | Were you sent here from the A/C System Performance Test? | Go to Step 2 | |||||||
2 |
Are the cooling fans ON and operating properly? | Go to Step 3 | Go to Step 5 | ||||||
3 | Visually inspect for the following:
Do any of these conditions exist? | Go to Step 4 | Go to Step 6 | ||||||
4 | Repair the air flow restriction. Is the action complete? | Go to Step 9 | -- | ||||||
5 | Repair the cooling fan operation fault. Refer to Cooling Fan Inoperative in Engine Cooling. Is the action complete? | Go to Step 9 | -- | ||||||
6 |
Caution: Refer to Moving Parts and Hot Surfaces Caution in the Preface section. Feel the liquid line on both sides of the expansion device. Is the temperature the same before and after the expansion device? | Go to Step 7 | Go to Step 8 | ||||||
7 | Replace the damaged or faulty orifice tube. Refer to Expansion (Orifice) Tube Replacement . Is the action complete? | Go to Step 9 | -- | ||||||
8 | Air is in the refrigerant system, or the system is overcharged. Refer to the view screen on the J 43600 for foreign gas content in the refrigerant. Recover and recharge the A/C system. Refer to Refrigerant Recovery and Recharging . Is the action complete? | Go to Step 9 | -- | ||||||
9 |
Are the readings within the specified ranges? | Go to Step 10 | |||||||
10 | Operate the system in order to verify the repair. Did you find and correct the condition? | System OK | Go to Symptoms - HVAC Systems - Manual in HVAC Systems - Manual |