This test resets HVAC control module (IPM) and tests for the current air temperature DTC.
The ambient air temperature must be above 3°C (38°F).
The specified values are from the A/C System Performance Test
Step | Action | Values | Yes | No | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Schematic Reference: HVAC Schematics DEFINITION: The cooling is insufficient. | ||||||||||||||
1 | Did you perform the HVAC Diagnostic System Check? | -- | Go to Step 2 | |||||||||||
Does the scan tool display DTC B1340 or B1341? | -- | Go to Step 3 | ||||||||||||
3 | Place the blower motor switch in each speed position. Does the blower motor operate in each speed position? | -- | Go to Step 4 | Go to Blower Motor Inoperative | ||||||||||
4 | Does the blower motor provide sufficient air flow? | -- | Go to Step 5 | Go to Blower Motor Malfunction | ||||||||||
5 |
Does the recirculation door move from the recirculation position to the ambient air position? | -- | Go to Step 6 | |||||||||||
6 | Does the Too Hot in Vehicle concern occur when A/C requested? | -- | Go to Step 7 | Go to Step 9 | ||||||||||
Important: Ambient air temperature must be above 3°C (38°F).
Does the A/C compressor clutch engage? | -- | Go to Step 8 | ||||||||||||
Perform the refrigerant system performance test. Refer to Air Conditioning (A/C) System Performance Test in Heating and Air Conditioning. Are pressure values within specifications for the ambient air temperature, and within 103 kpa (15 psi) of each other? | -- | Go to Step 9 | Go to Leak Testing in Heating, Ventilation and Air Conditioning | |||||||||||
9 |
Do the counts change when actuators are commanded? | -- | Go to Step 10 | Go to Step 16 | ||||||||||
10 | Check the air temperature sensors for proper installation. Refer to the following procedures: Did you find and correct the condition? | -- | Go to Step 26 | Go to Step 11 | ||||||||||
11 | Inspect for airflow through the inside air temperature assembly by placing a 5 cm (2 in) square piece of paper over the sensor air inlet. Does the paper stay in place? | -- | Go to Step 12 | Go to Step 18 | ||||||||||
12 |
Does the scan tool indicate that the sensor temperatures are within the specifications at the thermometer temperatures? | -3 to +3°C (-5 to +5°F) | Go to Step 13 | Go to Step 15 | ||||||||||
13 |
Does the scan tool indicate that the solar sensor parameter is greater than the specified value? | 230 Counts | Go to Step 14 | Go to Step 19 | ||||||||||
14 |
Do the counts change? | -- | Go to Testing for Intermittent Conditions and Poor Connections in Wiring Systems | Go to Step 19 | ||||||||||
15 | Test the suspect temperature sensor resistance. Refer to Sensor Resistance Table . Does the resistance measure near the Sensor Resistance Table? | -- | Go to Step 21 | Go to Step 18 | ||||||||||
16 | Test the suspect actuator door control circuit for a short to voltage, short to ground, open or high resistance. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 26 | Go to Step 17 | ||||||||||
17 | Test the suspect actuator ignition 3 voltage circuit for a short to ground, open or high resistance. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 26 | Go to Step 20 | ||||||||||
18 | Inspect for poor connections at the harness connector of the suspect air temperature sensor. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 26 | Go to Step 22 | ||||||||||
19 | Inspect for poor connections at the harness connector of the sunload sensor. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 26 | Go to Step 23 | ||||||||||
20 | Inspect for poor connections at the harness connector of the suspect air temperature actuator. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 26 | Go to Step 24 | ||||||||||
21 | Inspect for poor connections at the harness connector of the IPM. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 26 | Go to Step 25 | ||||||||||
22 | Replace the suspect temperature sensor. Refer to Air Temperature Sensor Replacement - Upper Left Side , Air Temperature Sensor Replacement - Upper Right Side , Air Temperature Sensor Replacement - Lower Left Side , Air Temperature Sensor Replacement - Lower Right Side or Inside Air Temperature Sensor Replacement . Did you complete the replacement? | -- | Go to Step 26 | -- | ||||||||||
23 | Replace the sunload sensor. Refer to Sun Load Sensor Replacement . Did you complete the replacement? | -- | Go to Step 26 | -- | ||||||||||
24 |
Important: Perform the recalibration procedure for the air temperature actuator. Replace the suspect air temperature actuator. Refer to Air Temperature Actuator Replacement - Right Side or Air Temperature Actuator Replacement - Left Side . Did you complete the replacement? | -- | Go to Step 26 | -- | ||||||||||
25 |
Important: Perform the recalibration procedure for the IPM. Replace the IPM. Refer to HVAC Control Module Replacement . Did you complete the replacement? | -- | Go to Step 26 | -- | ||||||||||
26 | Operate the system in order to verify the repair. Did you correct the condition? | -- | System OK | Go to Step 3 |