The number(s) below refer to the step number(s) on the diagnostic table.
Tests for voltage at the coil side of the recirculation vacuum solenoid valve. The heater and A/C control supplies power to the coil side of the recirculation vacuum solenoid valve.
Verifies that the heater and A/C control is providing ground to the recirculation vacuum solenoid valve.
Tests if ground is constantly being applied to the recirculation vacuum solenoid valve.
Step | Action | Value | Yes | No |
---|---|---|---|---|
Schematic Reference: HVAC Schematics DEFINITION: Air recirculation is inoperative or is always ON. | ||||
1 | Did you perform the HVAC Diagnostic System Check? | -- | Go to Step 2 | |
2 |
Does the scan tool indicate the Air Circulation Valve changes state? | -- | Go to Step 3 | Go to Step 11 |
3 |
Does the recirculation vacuum solenoid valve turn ON and OFF? | -- | Go to Testing for Intermittent Conditions and Poor Connections in Wiring Systems | Go to Step 4 |
Does the test lamp illuminate? | -- | Go to Step 5 | Go to Step 12 | |
Does the test lamp turn ON and OFF with each command? | -- | Go to Step 9 | Go to Step 6 | |
Does the test lamp remain illuminated with each command? | -- | Go to Step 8 | Go to Step 7 | |
7 | Test circuit 921 of the recirculation vacuum solenoid valve for an open. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 15 | Go to Step 11 |
8 | Test circuit 921 of the recirculation vacuum solenoid valve for a short to ground. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 15 | Go to Step 11 |
9 | Measure the resistance of the recirculation vacuum solenoid valve. Does the resistance measure near the specified range? | 35-40 ohms | Go to Step 15 | |
10 | Inspect for poor connections at the recirculation vacuum solenoid valve. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 15 | Go to Step 13 |
11 | Inspect for poor connections at the harness connector of the heater and A/C control. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 15 | Go to Step 14 |
12 | Test circuit 938/925 of the recirculation vacuum solenoid valve for an open, high resistance or a short to ground. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 15 | Go to Step 11 |
13 | Replace the recirculation vacuum solenoid valve. Refer to Vacuum Electrical Solenoid Replacement - Recirculation Actuator Control . Did you complete the replacement? | -- | Go to Step 15 | -- |
14 |
Important: Perform the recalibration procedure for the heater and A/C control. Replace the heater and A/C control. Refer to HVAC Control Module Replacement . Did you complete the replacement? | -- | Go to Step 15 | -- |
15 | Operate the system in order to verify the repair. Did you correct the condition? | -- | System OK | Go to Step 2 |