The numbers below refer to the step numbers on the diagnostic table.
This test resets HVAC control module and checks for current air temperature actuator DTC.
This checks for proper operation of coolant system to ensure heater output.
Step | Action | Values | Yes | No | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Schematic Reference: HVAC Schematics Connector End View Reference: HVAC Connector End Views DEFINITION: The temperature cannot be adjusted or the heating is insufficient. | ||||||||||||||||
1 | Did you perform the Diagnostic System Check - Vehicle? | -- | Go to Step 2 | |||||||||||||
Does the scan tool display DTCs? | -- | Go to Step 3 | ||||||||||||||
3 | Place the blower motor switch in each speed position. Does the blower motor operate in any speed position? | -- | Go to Step 4 | Go to Blower Motor Inoperative | ||||||||||||
4 | Does the blower motor operate at the desired speeds? | -- | Go to Step 5 | Go to Blower Motor Malfunction | ||||||||||||
5 |
Does the recirculation door move from the recirculation position to the ambient air position? | -- | Go to Step 6 | |||||||||||||
6 | Does the Too Cold in Vehicle concern occur when heating or defrosting is desired? | -- | Go to Step 7 | Go to Step 9 | ||||||||||||
7 |
Does the A/C compressor operate? | -- | Go to Step 8 | |||||||||||||
Inspect the cooling system for the following conditions:
Did you find and correct the condition? | -- | Go to Step 24 | Go to Step 9 | |||||||||||||
9 | Inspect the upper and lower air temperature sensors for the following conditions:
Did you find and correct the condition? | -- | Go to Step 24 | Go to Step 10 | ||||||||||||
10 |
Does the paper stay in place? | -- | Go to Step 11 | Go to Step 14 | ||||||||||||
11 |
For the upper and lower duct temp parameter conversion from counts to temp, refer to Sensor Resistance Table . Does the scan tool indicate that the sensor temperatures are within the specification at the thermometer temperatures? | -3 to +3°C (-5 to +5°F) | Go to Step 12 | Go to Step 17 | ||||||||||||
12 |
Does the scan tool indicate that the sunload sensor parameter is greater than the specified value? | 224 Counts | Go to Step 13 | Go to Step 19 | ||||||||||||
13 |
Do the counts change? | -- | System OK | Go to Step 19 | ||||||||||||
14 | Test the ignition 3 voltage circuit of the HVAC control module for a high resistance or an open. Refer to Circuit Testing and Wiring Repairs . Did you find and correct the condition? | -- | Go to Step 24 | Go to Step 15 | ||||||||||||
15 | Test the battery positive voltage circuit of the HVAC control module for a high resistance or an open. Refer to Circuit Testing and Wiring Repairs . Did you find and correct the condition? | -- | Go to Step 24 | Go to Step 16 | ||||||||||||
16 | Test the ground circuit of the HVAC control module for a high resistance or an open. Refer to Circuit Testing and Wiring Repairs . Did you find and correct the condition? | -- | Go to Step 24 | Go to Step 20 | ||||||||||||
17 | Test the suspect temperature sensor resistance. Refer to Sensor Resistance Table . Does the resistance measure near the Sensor Resistance Table? | -- | Go to Step 20 | Go to Step 18 | ||||||||||||
18 | Inspect for poor connections at the harness connector of the suspect air temperature sensor. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs . Did you find and correct the condition? | -- | Go to Step 24 | Go to Step 21 | ||||||||||||
19 | Inspect for poor connections at the harness connector of the sunload sensor. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs . Did you find and correct the condition? | -- | Go to Step 24 | Go to Step 22 | ||||||||||||
20 | Inspect for poor connections at the harness connector of the HVAC control module. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs . Did you find and correct the condition? | -- | Go to Step 24 | Go to Step 23 | ||||||||||||
21 | Replace the appropriate temperature sensor. Refer to the following procedures: Did you complete the replacement? | -- | Go to Step 24 | -- | ||||||||||||
22 | Replace the ambient light sensor. Refer to Ambient Light Sensor Replacement . Did you complete the replacement? | -- | Go to Step 24 | -- | ||||||||||||
23 | Replace the HVAC control module. Refer to Control Module References for replacement, setup, and programming. Did you complete the replacement? | -- | Go to Step 24 | -- | ||||||||||||
24 | Operate the system in order to verify the repair. Did you correct the condition? | -- | System OK | Go to Step 3 |