The HVAC control module monitors the inside air temperature with an inside air temperature sensor. When the air is cold, the sensor resistance and signal voltage are high. When the air is warm, the sensor resistance and signal voltage are low. The HVAC control module requests A/C compressor clutch engagement and controls the air temperature actuator door positions in order to maintain the selected air temperature.
The ignition is turned ON.
The HVAC control module detects the signal circuit is less than 0.09 V.
• | The HVAC control module will store the trouble code in memory. |
• | A default value will be used for the sensor data by the HVAC control module to allow the system to operate. |
• | The DTC will become history if the HVAC control module no longer detects a failure. |
• | The history DTC will clear after 100 fault free ignition cycles. |
• | The DTC can be cleared with a scan tool. |
If condition not present, refer to Testing for Intermittent Conditions and Poor Connections in Wiring Systems.
The numbers below refer to the step numbers on the diagnostic table.
Tests for the proper operation of the circuit in the high voltage range.
Tests for the proper operation of the circuit in the low voltage range. If the fuse in the jumper opens when you perform this test, the signal circuit is shorted to voltage.
Step | Action | Values | Yes | No |
---|---|---|---|---|
Schematic Reference: HVAC Schematics | ||||
1 | Did you perform the HVAC Diagnostic System Check? | -- | Go to Step 2 | |
2 |
Does the scan tool indicate that the Inside Temp Sensor parameter is within the specified range? | 0.09-4.90 V | Go to Diagnostic Aids | Go to Step 3 |
Does the scan tool indicate that the Inside Temp Sensor parameter is greater than the specified value? | 4.90 V | Go to Step 4 | Go to Step 5 | |
Does the scan tool indicate that the Inside Temp Sensor parameter is less than the specified value? | 0.09 V | Go to Step 8 | Go to Step 6 | |
5 | Test the signal circuit of the inside air temperature sensor for a short to ground. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 12 | Go to Step 9 |
6 | Test the signal circuit of the inside air temperature sensor for a short to voltage, a high resistance, or an open. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 12 | Go to Step 7 |
7 | Test the low reference circuit of the inside air temperature sensor for a high resistance or an open. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 12 | Go to Step 9 |
8 | Inspect for poor connections at the harness connector of the inside air temperature sensor. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 12 | Go to Step 10 |
9 | Inspect for poor connections at the harness connector of the HVAC control module. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 12 | Go to Step 11 |
10 | Replace the inside air temperature sensor. Refer to Inside Air Temperature Sensor Replacement . Did you complete the replacement? | -- | Go to Step 12 | -- |
11 |
Important: Perform the recalibration procedure for the HVAC control module. Replace the HVAC control module. Refer to HVAC Control Module Replacement . Did you complete the replacement? | -- | Go to Step 12 | -- |
12 |
Does the DTC reset? | -- | Go to Step 2 | System OK |