Table 1: | Vacuum Actuator Table |
Control Setting | Solenoid 1 Yellow Vacuum Line Function HEATER/DEFROST | Solenoid 2 Brown Vacuum Line Function A/C | Solenoid 3 Red Vacuum Line Function HEATER | Solenoid 4 Blue Vacuum Line Function DEFROST | Solenoid 5 Orange Vacuum Line Function AIR/INLET |
---|---|---|---|---|---|
Fan-OFF (Mode-Auto) | ON | OFF | ON | OFF | OFF |
Fan-Med. Speed (Mode-Panel) | OFF | ON | ON | OFF | OFF |
Fan-Med. Speed (Mode-Panel/Floor)) | OFF | OFF | ON | OFF | OFF |
Fan-Med. Speed (Mode-Floor) | ON | OFF | ON | OFF | OFF |
Fan-Med. Speed (Mode-Floor/ Windshield) | ON | OFF | OFF | OFF | OFF |
Fan-Med. Speed (Mode-Defrost) | ON | OFF | OFF | ON | OFF |
NOTE: Ensure the preliminary settings of the A/C are set on the dial temperature 28°C (82°F) and the ambient temperature 21°C (70°F). |
Step | Action | Value(s) | Yes | No | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
1 | Was the Diagnostic System Check performed? | -- | Go to Step 2 | Go to A Diagnostic System Check | ||||||||
2 | Verify that the blower motor is inoperative at any speed. Does the blower motor operate normally? | -- | Go to Testing for Intermittent Conditions and Poor Connections in Wiring Systems | Go to Step 3 | ||||||||
3 |
Does the air flow not change in any mode switch position? | -- | Go to Step 4 | Go to Step 8 | ||||||||
4 |
Are the solenoids operating correctly? | -- | Go to Step 5 | Go to Step 6 | ||||||||
5 | Install a vacuum gauge on the vacuum line (GRY) of the HVAC solenoid assembly. Is vacuum present in the system? | -- | Go to Step 12 | Go to Step 7 | ||||||||
6 |
Is the repair complete? | -- | Go to Step 13 | -- | ||||||||
7 | Inspect the vacuum hoses and repair any of the following conditions:
Is the repair complete? | -- | Go to Step 13 | -- | ||||||||
8 |
Do any of the conditions exist? | -- | Go to Step 9 | Go to Step 10 | ||||||||
9 | Repair a faulty circuit from Step 8. Is the repair complete? | -- | Go to Step 13 | -- | ||||||||
10 |
Is the reading as specified? | 9-16 V | Go to Step 11 | Go to Step 12 | ||||||||
11 | Replace the ECC module. Is the replacement complete? | -- | Go to Step 13 | -- | ||||||||
12 | Replace the HVAC solenoid assembly. Is the replacement complete? | -- | Go to Step 13 | -- | ||||||||
13 | Operate the system in order to verify the repair. Did you correct the condition? | -- | System OK | Go to Step 3 |