The Cycling Clutch Orifice Tube (CCOT) refrigerant system is used on vehicles that are equipped with 4.3L engines. The CCOT refrigeration system cycles a compressor on and off. the cycles maintain desired cooling and prevents evaporator freeze-up. Passenger compartment comfort is maintained by selecting the following on the control assembly:
• | The mode. |
• | The fan speed. |
• | The air temperature. |
The refrigeration cycle is controlled by a switch that senses low-side pressure as an indicator of evaporator pressure. The switch is the freeze protection device in the system that senses refrigerant pressure on the suction side of the system. The switch is located on the low-side service fitting, which is standard for this system. The equalized pressures within the charged air conditioning system close the contacts of the pressure switch when the air temperature is between 16°-26°C (60°-80°F).
Voltage is supplied to the compressor coil switch when an air conditioning mode is selected. The compressor reduces the evaporator pressure to approximately 175 kPa (25 psi). The pressure switch then opens, which de-energizes the compressor clutch. As the pressure system equalizes and the pressure reaches approximately 315 kPa (46 psi), the pressure switch contacts close. This re-energizes the clutch coil.
Under certain conditions, cycling may cause increases and decreases of engine speed. This is a normal condition. The system is designed to maintain desired cooling, which prevents evaporator freeze-up.
The operating characteristics of the low-side pressure cycling switch provides additional compressor protection. Low-side pressures could be insufficient to close the contacts of the pressure switch under the following conditions:
• | A massive discharge occurs in the low side of the system. |
• | The orifice tube becomes unplugged. |
If a low charge occurs, insufficient cooling accompanied by rapid compressor clutch cycling will be noticed at high air temperatures.
When the engine is turned OFF while the air conditioning system is operating, the refrigerant in the system will continue to flow. The refrigerant will flow from the high-pressure side of expansion tube (orifice) to the low pressure side until the pressure is equalized. The equalization can be detected as a hissing sound for 30-60 seconds. This is a normal condition.
Step | Action | Value(s) | Yes | No | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
1 | Did you perform the Functional Check? | -- | Go to Step 2 | Go to Function Test | ||||||||
2 | Inspect the following components of the A/C system:
Did you find and repair a condition? | -- | Go to Function Test | Go to Step 3 | ||||||||
3 | Inspect the drive belt. Does the drive belt operate properly? | -- | Go to Step 4 | Go to Step 5 | ||||||||
4 |
Important: The ambient temperature must be above 10°C (50°F) for completion of this diagnostic procedure. Inspect the compressor clutch engagement by following these steps:
Idle the engine. Does the clutch engage or cycle? | -- | Go to Step 8 | Go to Step 12 | ||||||||
5 | Has the compressor seized? | -- | Go to Step 6 | Go to Step 7 | ||||||||
6 |
Are the repairs complete? | -- | Go to Function Test | -- | ||||||||
7 | Replace the belt. Is the repair complete? | -- | Go to Step 4 | -- | ||||||||
8 | Feel the liquid line before the orifice tube. Is the liquid line cold? | -- | Go to Step 9 | Go to Step 10 | ||||||||
9 |
Is the repair complete? | -- | Go to Function Test | -- | ||||||||
10 |
Is the inlet pipe slightly colder than the outlet pipe? | -- | Go to Step 11 | Go to Step 25 | ||||||||
11 |
Did you find and repair a leak? | -- | Go to Function Test | Go to Step 21 | ||||||||
12 |
Does the compressor clutch engage? | -- | Go to Step 13 | Go to Step 19 | ||||||||
13 |
Is the pressure below the specified value? | 345 kPa (50 psi) | Go to Step 14 | Go to Step 16 | ||||||||
14 | Inspect the refrigerant pressure on the high side of the system. Is the pressure above the specified value? | 345 kPa (50 psi) | Go to Step 15 | Go to Step 11 | ||||||||
15 |
Is the repair complete? | -- | Go to Function Test | -- | ||||||||
16 | Connect a fused jumper wire between the pressure switch and the positive battery post. Does the compressor operate? | -- | Go to Step 17 | Go to Step 18 | ||||||||
17 |
Important: Do not recover the refrigerant. Is the repair complete? | -- | Go to Function Test | -- | ||||||||
18 |
Is the repair complete? | -- | Go to Function Test | -- | ||||||||
19 | Apply an external ground to the compressor. Does the compressor clutch engage? | -- | Go to Function Test | Go to Step 20 | ||||||||
20 | Rebuild the compressor. Is the repair complete? | -- | Go to Function Test | -- | ||||||||
21 |
Is the clutch cycle rate greater than the specified value? | 8 cycles /minute | Go to Step 22 | Go to Step 23 | ||||||||
22 |
Is the repair complete? | -- | Go to Function Test | -- | ||||||||
23 |
Is the inlet pipe colder than the outlet pipe? | -- | Go to Step 24 | Go to Function Test | ||||||||
24 |
Is the inlet pipe warmer than the outlet pipe? | -- | Go to Step 22 | Go to Function Test | ||||||||
25 |
Does the compressor cycle on within the specified value range? | 280-350 kPa (41-51 psi) | Go to Step 26 | Go to Step 28 | ||||||||
26 | Does the compressor cycle off within the specified value range? | 140-190 kPa (20-28 psi) | Go to Step 27 | Go to Step 28 | ||||||||
27 |
Is the temperature performance within the limits of the test specifications? | -- | Go to Function Test | Go to Step 32 | ||||||||
28 | Does the compressor cycle high on above the specified value? | 350 kPa (51 psi) | Go to Step 29 | Go to Step 30 | ||||||||
29 | Does the compressor cycle OFF below the specified value? | 140 kPa (20 psi) | Go to Step 17 | Go to Step 32 | ||||||||
30 |
Does the compressor cycle OFF below the specified value range? | 140 kPa (20 psi) | Go to Step 17 | Go to Step 31 | ||||||||
31 | Reconnect the blower motor wire. Is the wire reconnected? | -- | Go to Step 27 | -- | ||||||||
32 | Observe the compressor cycling. Does the compressor cycle on continuously? | -- | Go to Step 33 | Go to Step 22 | ||||||||
33 |
Is the orifice missing? | -- | Go to Step 34 | Go to Step 35 | ||||||||
34 |
Is the repair complete? | -- | Go to Function Test | -- | ||||||||
35 | Inspect the suction line. Is the suction line restricted? | -- | Go to Step 36 | Go to Step 37 | ||||||||
36 | Repair the suction line, as required. Is the repair complete? | -- | Go to Function Test | -- | ||||||||
37 |
Is the repair complete? | -- | Go to Function Test | -- |