The HVAC control module monitors the ambient air temperature via an ambient air temperature sensor. When the air is cold, the sensor resistance and signal voltage are high. When the air is warm, the sensor resistance and signal voltage are low. The HVAC control module displays the outside air temperature on the HVAC control module.
The ignition is turned ON.
The HVAC control module detects the signal circuit is less than 0.09 volts.
• | The HVAC control module uses a default value. |
• | The HVAC control module will display " - -" for ambient air temperature when OFF. |
• | The DTC will become history if the HVAC control module no longer detects a failure. |
• | The history DTC will clear after 50 fault free ignition cycles. |
• | The DTC can be cleared with a scan tool. |
If condition not present refer to Testing for Intermittent Conditions and Poor Connections in Wiring Systems.
The number(s) below refer to the step number(s) on the diagnostic table.
Tests for the proper operation of the circuit in the high voltage range.
Tests for the proper operation of the circuit in the low voltage range. If the fuse in the jumper opens when you perform this test, the signal circuit is shorted to voltage.
Step | Action | Value(s) | Yes | No |
---|---|---|---|---|
Schematic Reference: HVAC Schematics | ||||
1 | Did you perform the HVAC Diagnostic System Check? | -- | Go to Step 2 | |
2 |
Does the scan tool indicate that the Outside Temp Sensor parameter is within the specified range? | 0.09-4.90 V | Go to Diagnostic Aids | Go to Step 3 |
Does the scan tool indicate that the Outside Temp Sensor parameter is greater than the specified value? | 4.90 V | Go to Step 4 | Go to Step 5 | |
Does the scan tool indicate that the Outside Temp Sensor parameter is less than the specified value? | 0.09 V | Go to Step 8 | Go to Step 6 | |
5 | Test the signal circuit of the ambient air temperature sensor for a short to ground. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 12 | Go to Step 9 |
6 | Test the signal circuit of the ambient air temperature sensor for a short to voltage, a high resistance, or an open. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 12 | Go to Step 7 |
7 | Test the low reference circuit of the ambient air temperature sensor for a high resistance or an open. Refer to Circuit Testing and Wiring Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 12 | Go to Step 9 |
8 | Inspect for poor connections at the harness connector of the ambient air temperature sensor. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 12 | Go to Step 10 |
9 | Inspect for poor connections at the harness connector of the HVAC control module. Refer to Testing for Intermittent Conditions and Poor Connections and Connector Repairs in Wiring Systems. Did you find and correct the condition? | -- | Go to Step 12 | Go to Step 11 |
10 | Replace the ambient air temperature sensor. Refer to Ambient Air Temperature Sensor Replacement . Did you complete the replacement? | -- | Go to Step 12 | -- |
11 | Replace the HVAC control module. Refer to HVAC Control Module Replacement . Did you complete the replacement? | -- | Go to Step 12 | -- |
12 |
Does the DTC reset? | -- | Go to Step 2 | System OK |